Data Mining on Partial Discharge Signals of Power Transformer’s Defect Models
, Ph.D. Dissertation Sharif University of Technology ; Vakilian, Mehdi (Supervisor) ; Phung, Bao Toan (Co-Advisor) ; Blackburn, Trevor (Co-Advisor)
Abstract
In this thesis the goal is to use data Mining techniques for finding features of different Partial discharges happen in power transformer insulation defect models in order to monitor the insulation condition of in-service power transformers continuously and on-line and to identify any type of insulation defect in power transformers at the early stage of formation.For this purpose, power transformer Insulation defects are modeled physically and partial discharge current pulses are recorded as Partial discharge data.Tow format of data are investigated, in first one, recorded data in one power frequency cycle are explored and in second one, individual PD pulses are considered for study.In...
A method for optimal coordinated insulation design of transmission line
, Article Australian Journal of Electrical and Electronics Engineering ; Volume 7, Issue 3 , 2010 , Pages 211-223 ; 1448837X (ISSN) ; Vakilian, M ; Blackburn, T. R ; Sharif University of Technology
2010
Abstract
The first step in the accepted methods of overhead transmission line insulation coordination is to specify a reliability criterion, and then based on this constraint the most economic insulation design is sought. While the objective of an optimal insulation design method is to find an insulation design that minimises the total cost (the sum of the installation cost, operational cost and cost of failure), each of the cost components can be determined on a per-year basis taking into account the equipment's lifetimes. In this paper, through application of ATP software and realising the total cost of different transmission line designs, a set of alternative insulation designs using various surge...
Transformer components impact on compatibility of measured PDs: Comparison of IEC60270 and RF methods
, Article High Voltage ; Volume 4, Issue 1 , 2019 , Pages 33-40 ; 23977264 (ISSN) ; Vakilian, M ; Toan Phung, B ; Blackburn, T ; Sharif University of Technology
Institution of Engineering and Technology
2019
Abstract
Power transformer partial discharge signal measurement using Radio Frequency method has advantages over IEC 60270 'apparent charge' measurement method for online monitoring due to greater immunity against external interference. However, the lack of a well-defined calibration relationship between the two methods is main disadvantage of RF method. Simultaneous measurements, using these two methods, carried out on various transformer PD source models, in laboratory, to investigate main parameters that affect the relationship of results of these two methods. In this paper, factors that influence this relationship are classified into three groups: (i) type of PD sources, (ii) transformer windings...
Partial discharges pattern recognition of transformer defect model by LBP & HOG features
, Article IEEE Transactions on Power Delivery ; 2018 ; 08858977 (ISSN) ; Vakilian, M ; Phung, B. T ; Blackburn, T. R ; Sharif University of Technology
Institute of Electrical and Electronics Engineers Inc
2018
Abstract
Partial discharge (PD) measurement and identification have great importance to condition monitoring of power transformers. In this paper a new method for recognition of single and multi-source of PD based on extraction of high level image features have been introduced. A database, involving 365 samples of phase-resolved PD (PRPD) data, is developed by measurement carried out on transformer artificial defect models (having different sizes of defect) under a specific applied voltage, to be used for proposed algorithm validation. In the first step, each set of PRPD data is converted into grayscale images to represent different PD defects. Two “image feature extraction” methods, the Local Binary...
A Hybrid transformer pd monitoring method using simultaneous iec60270 and rf data
, Article IEEE Transactions on Power Delivery ; Volume 34, Issue 4 , 2019 , Pages 1374-1382 ; 08858977 (ISSN) ; Vakilian, M ; Phung, B. T ; Blackburn, T. R ; Sharif University of Technology
Institute of Electrical and Electronics Engineers Inc
2019
Abstract
Transformers are the key component in power system transmission and distribution networks. Condition-based maintenance will increase their expected life, and online monitoring is essential to ensure operation reliability. In this paper, a new approach to transformer online monitoring is provided based on partial discharge (PD) measurement. Simultaneous measurements of PD using IEC60270 and radio frequency (RF) techniques are employed to explore new features that can be used to distinguish between internal PDs and external interference, as well as among different internal PD sources. Stream clustering based on the density grid method with only a few features required is used to categorize...
Partial discharges pattern recognition of transformer defect model by LBP & HOG features
, Article IEEE Transactions on Power Delivery ; Volume 34, Issue 2 , 2019 , Pages 542-550 ; 08858977 (ISSN) ; Vakilian, M ; Phung, B. T ; Blackburn, T. R ; Sharif University of Technology
Institute of Electrical and Electronics Engineers Inc
2019
Abstract
Partial discharge (PD) measurement and identification have great importance to condition monitoring of power transformers. In this paper, a new method for recognition of single and multi-source of PD based on extraction of high level image features has been introduced. A database, involving 365 samples of phase-resolved PD (PRPD) data, is developed by measurement carried out on transformer artificial defect models (having different sizes of defect) under a specific applied voltage, to be used for proposed algorithm validation. In the first step, each set of PRPD data is converted into grayscale images to represent different PD defects. Two 'image feature extraction' methods, the Local Binary...
Direct introduction of semicon layers in XLPE cable model
, Article 2006 International Conference on Power System Technology, POWERCON2006, Chongqing, 22 October 2006 through 26 October 2006 ; 2006 ; 1424401119 (ISBN); 9781424401116 (ISBN) ; Vakilian, M ; Blackburn, T. R ; Phung, B. T ; Sharif University of Technology
Institute of Electrical and Electronics Engineers Inc
2006
Abstract
Detection and location of any partial discharge signal requires an accurate frequency dependent cable model to correctly simulate the P.D. signal attenuation during its propagation in the cable. This model should be capable of simulating the semiconducting layers which have significant effects on P.D. signal attenuation and its propagation velocity. There is a substantial need for improvements in the flexibility of transient cable model through direct introduction of the two semiconducting layers in the cable model. This can be employed, in the next step to develop a 3 phase cable model for ATP. This paper has derived an impedance formula for the semiconducting layers. The propagation...
An efficient diagnosis method for data mining on single PD pulses of transformer insulation defect models
, Article IEEE Transactions on Dielectrics and Electrical Insulation ; Volume 20, Issue 6 , 2013 , Pages 2061-2072 ; 10709878 (ISSN) ; Vakilian, M ; Phung, B. T ; Blackburn, T. R ; Sharif University of Technology
Institute of Electrical and Electronics Engineers Inc
2013
Abstract
Reviewing the various Partial Discharges (PD data mining researches which have been reported so far, this study compares the performance of different feature spaces and different classifiers employed for PD classification in insulation condition monitoring of power transformers. In this process, first a knowledge basis is developed through construction of 4 different types of PD models in the high voltage laboratory. Background noise is considered as one class in this knowledge basis. The high frequency time domain current signals of high voltage equipment are captured over one power frequency cycle. The single PD activities within this captured signal are extracted by application of a...
An efficient PD data mining method for power transformer defect models using SOM technique
, Article International Journal of Electrical Power and Energy Systems ; Volume 71 , October , 2015 , Pages 373-382 ; 01420615 (ISSN) ; Vakilian, M ; Blackburn, T. R ; Phung, B. T ; Sharif University of Technology
Elsevier Ltd
2015
Abstract
Suggestion and application of a set of new features for on-line Partial Discharge (PD) monitoring, where there is no information about the type of PD is a challenging task for condition assessment of power equipments, such as a power transformer. This is looked for in this paper. So far, in past various techniques have been employed to develop a comprehensive PD monitoring system, however limited success has been achieved. One of the challenging issues in this field is the discovering of proper features capable of differentiating the involvement of possible types of PD sources. In order to examine the efficiency of the method established in this paper, which is based on application of a set...
A method to capture and de-noise partial discharge pulses using discrete wavelet transform and ANFIS
, Article International Transactions on Electrical Energy Systems ; Volume 25, Issue 11 , September , 2015 , Pages 2696-2712 ; 20507038 (ISSN) ; Hajipour, E ; Vakilian, M ; Akbari, A ; Blackburn, T ; Phung, B. T ; Sharif University of Technology
John Wiley and Sons Ltd
2015
Abstract
Due to the presence of excessive noise in the recorded partial discharge (PD) current signals, de-noising of these signals is a crucial task for performing any investigation on the subject. Meanwhile, to accelerate this de-noising process a single PD pulse can be extracted from the train of those recorded pulses, followed by its de-noising. In this paper a single PD pulse is extracted from the train of recorded PD pulses, using noisy recorded data cumulative energy. A de-noising technique based on adaptive neuro-fuzzy inference systems is proposed. To verify the validity of the proposed method, four different sources of PD signals are physically simulated. The proposed method is applied on...
Investigation of partial discharge propagation and location in multiple-α and single- α transformer windings using optimized wavelet analysis
, Article Iranian Journal of Science and Technology, Transaction B: Engineering ; Volume 30, Issue 6 , 2006 , Pages 655-666 ; 03601307 (ISSN) ; Vakilian, M ; Blackburn, T. R ; Phung, T. B ; Salay Naderi, M ; Sharif University of Technology
2006
Abstract
Partial discharges (PD) are recognized as the main cause of the inner insulation deterioration process in power transformers. Therefore, the optimum inner insulation design is one of the challenges a transformer designer is faced with. Transformer strength, especially during transient conditions, is a criterion for transformer insulation designers. This challenge has made designers initiate and employ other types of winding, for example, rather than ordinary layer and disc windings employ the multiple-α windings. Multiple-α windings have a more complicated structure and are comprised of various parts with different physical structures and electrical characteristics. Typical partial discharge...
A hybrid transformer model for determination of partial discharge location in transformer winding
, Article IEEE Transactions on Dielectrics and Electrical Insulation ; Volume 14, Issue 2 , 2007 , Pages 436-443 ; 10709878 (ISSN) ; Vakilian, M ; Blackburn, T. R ; Phung, B. T ; Naderi, M. S ; Nasiri, A ; Sharif University of Technology
2007
Abstract
Partial discharges are well known as a source for insulation degradation in power transformers. A hybrid transformer model is introduced to simulate the transformer winding transient response. Transformer structural data is used to determine the hybrid model parameters. Calculations of the hybrid transient model parameters are based on the parameters of the lumped parameter equivalent transformer model and electromagnetic rules. Modern computation techniques and optimizations are employed beside this model for PD location using the multi conductor transmission line model and also to analyze its propagation aimed at achieving (i) more reliable simulation results (ii) less computational time...
A method for studying partial discharges location and propagation within power transformer winding based on the structural data
, Article 2005 International Symposium on Electrical Insulating Materials, ISEIM 2005, Kitakyushu, 5 June 2005 through 9 June 2005 ; Volume 2 , 2005 , Pages 490-493 ; Vakilian, M ; Blackburn, T. R ; Phung, B. T ; Zhang, H ; Naderi, M. S ; Sharif University of Technology
Institute of Electrical Engineers of Japan
2005
Abstract
Power transformer inner insulation system is a very critical component. Its degradation may pose apparatus to fail while in service. On the other hand, experimental experiences prove that partial discharges are a major source of insulation failure in power transformers. If the deterioration of the insulation system caused by PD activity can be detected at an early stage, preventive maintenance measures may be taken. Because of the complex structure of the transformer, accurate PD location is difficult and is one of the challenges power utilities are faced with. This problem comes to be vital in open access systems. In this paper a theory for locating partial discharge and its propagation...
An optimal wavelet filtering method for noise suppression of PD measured signal and its location in power transformer winding
, Article 2005 IEEE International Conference on Dielectric Liquids, ICDL 2005, Coimbra, 26 June 2005 through 1 July 2005 ; 2005 , Pages 269-272 ; 0780389549 (ISBN); 9780780389540 (ISBN) ; Vakilian, M ; Blackburn, T. R ; Phung, B. T ; Nam O, H ; Naderi, M. S ; Sharif University of Technology
2005
Abstract
In this paper a method for selecting optimal wavelet is introduced, which is implemented for evaluating electrical measured partial discharges on a 66 kV/25 MVA fully interleaved winding of a power transformer. Applying wavelet transform to a signal produces a wavelet detail coefficient distribution throughout the time-scale, which depends on the wavelet chosen. This method is based on the capability of the chosen wavelet for generating coefficients with maximal values. The basic idea of this method is described and applications to partial discharge studies are explored. The paper demonstrates that the wavelet based de-noising method proposed in the paper can be employed in extracting the PD...
A comparison between partial discharge propagation in multiple-α and single-α transformer winding
, Article Electrical Insulation Conference and Electrical Manufacturing Expo, 2005, Indianapolis, IN, 23 October 2005 through 26 October 2005 ; Volume 2005 , 2005 , Pages 108-111 ; 0780391454 (ISBN); 9780780391451 (ISBN) ; Vakilian, M ; Blackburn, T. R ; Phung, B.T ; Zhang, H ; Nam O, H ; Naderi, M. S ; Sharif University of Technology
2005
Abstract
Power transformers are in service in different environmental, electrical and mechanical conditions. Many experiences have proved that the inner insulation system degradation may pose the transformer to fail while in service. On the other hand, partial discharges (PD) are recognized as the main cause of insulation deterioration process. Therefore, reaching the optimum inner insulation system is one of the challenges a transformer designer is faced with. The solution lies in the correct and accurate modelling of different types of transformer windings. Transformer strength especially during transient conditions is a criterion for transformer insulation designers. This challenge has made...
Simulation of partial discharge propagation and location in Abetti winding based on structural data
, Article 7th International Power Engineering Conference, IPEC2005, Singapore, 29 November 2005 through 2 December 2005 ; Volume 2005 , 2005 ; 9810544693 (ISBN); 9789810544690 (ISBN) ; Vakilian, M ; Blackburn, T. R ; Phung, B. T ; Hio, N. O ; Naderi, M. S ; Ghaemmaghami, R ; Sharif University of Technology
IEEE Computer Society
2005
Abstract
Power transformer monitoring as a reliable tool for maintaining purposes of this valuable asset of power systems has always comprised partial discharge offline measurements and online monitoring. The reason lies in non-destructive feature of PD monitoring. Partial discharge monitoring helps to detect incipient insulation faults and prevent insulation failure of power transformers. This paper introduces a software package developed based on structural data of power transformer and discusses the results of the simulation on Abetti winding, which might be considered as a basic layer winding. A hybrid model is used to model the transformer winding, which has been developed by first author....
LYSO based precision timing calorimeters
, Article Journal of Physics: Conference Series, 15 May 2016 through 20 May 2016 ; Volume 928, Issue 1 , 2017 ; 17426588 (ISSN) ; Apresyan, A ; Ronzhin, A ; Xie, S ; Duarte, J ; Spiropulu, M ; Trevor, J ; Anderson, D ; Pena, C ; Hassanshahi, M. H ; Sharif University of Technology
2017
Abstract
In this report we outline the study of the development of calorimeter detectors using bright scintillating crystals. We discuss how timing information with a precision of a few tens of pico seconds and below can significantly improve the reconstruction of the physics events under challenging high pileup conditions to be faced at the High-Luminosity LHC or a future hadron collider. The particular challenge in measuring the time of arrival of a high energy photon lies in the stochastic component of the distance of initial conversion and the size of the electromagnetic shower. We present studies and measurements from test beams for calorimeter based timing measurements to explore the ultimate...